Voltmasters Platform
Meter data analysis
Insights from the official Fluvius quarter-hour values of your grid connection: offtake and injection, monthly peaks and their capacity tariff, consumption profile, and what a battery needs to lower your peaks.
The Meter data analysis turns the official quarter-hour values Fluvius publishes for your grid connection into insights: how much you took from the grid and fed back, when your peaks fall, what they cost on the capacity tariff, and what a battery would need to lower them.
It works on the data of a Fluvius data mandate, so it needs no EMS controller or devices on site. As soon as a mandate is approved and Fluvius has published data, the analysis is available. See Data mandate and comparison to request a mandate.
Opening the analysis
Open it from the project menu under Analysis, Reports, Meter data analysis. The menu item appears on projects with an approved Fluvius mandate, and stays when a mandate has ended but still has data. The analysis then shows the data up to the last published day, with a notice that no new values come in. Every user with access to the project can open it: clients, installers and administrators.
On a project with a mandate but no devices yet, the Overview shows a notice with a View the analysis button, because the meter data is then the only data the project has.

The notice on the overview of a project that only has meter data so far.
Choosing a period and a meter point
- Period: by default the last 12 full months, because the capacity tariff is settled per calendar month. You can also pick This year, Last year, Last month, or any range in the date picker. A period covers at most 366 days.
- EAN: when the project has more than one approved mandate, a selector picks the meter point. With one mandate, the line above the tiles names the EAN.
Fluvius publishes its values with a delay of a day or more, so the date picker stops at the last published day. A mandate that has not delivered a full month yet opens on everything it has so far.
When Fluvius has not published 2% or more of the quarter-hours in the selected period, a warning above the tiles says how much is missing. Totals and peaks then only cover the quarter-hours that are available.
Key figures

The key figures of one year of meter data.
| Tile | What it is |
|---|---|
| Offtake | All energy taken from the grid in the period. |
| Injection | All energy fed back into the grid in the period. |
| Highest quarter-hour peak | The highest average offtake power of a single quarter-hour, with the day and time it happened. |
| Average monthly peak | The average of the highest quarter-hour of every month. This is what the capacity tariff is charged on. |
| Cost of monthly peaks | Every monthly peak multiplied by the capacity tariff of the project, added up over the months in the period. The tile only appears when the project has a capacity tariff, see below. |
| Night base load | The median offtake between 01:00 and 04:00: what keeps running when nobody works and the sun does not shine, such as cooling, ventilation, servers and standby. |
| Load factor | The average power over the period as a share of the highest peak. A low load factor means a few short peaks set the capacity tariff while the site mostly runs far below them. |
| Outside working hours | The share of the offtake outside weekdays from 07:00 to 18:00. Public holidays count as working days, because the platform does not know them. |
The capacity tariff is the Capacity tariff (consumption) in the grid settings of the project. Without an entered value, a Flemish project uses the tariff of its grid area. The current tariff is applied to the whole period.
Monthly overview

Offtake and injection per month, and the peak of every month against the average.
- Offtake and injection per month: offtake above the zero line, injection below it. The tooltip shows the exact values.
- Monthly peaks: the highest quarter-hour of every month, with the average monthly peak as a dashed line. The tooltip shows when the peak happened. The months above the line are the ones that raise the capacity tariff the most.
Average day profile

The average power per quarter-hour of the day, weekdays against weekends.
The day profile shows the average power for every quarter-hour of the day, split into weekdays and weekends, for both offtake and injection. Injection is drawn below the zero line. It shows when the site starts and stops working, how deep the lunch dip goes, and how much solar power is left over on days off. The download button exports the values.
Offtake per hour of the day

Every day of the period at a glance, hour by hour.
Every column is a day, every row an hour. The stronger the colour, the higher the average offtake in that hour; the legend underneath gives the scale. Weekends, holidays, shifts and the effect of the solar panels in summer stand out at once. Hover a cell for the day, the hour and the power.
Peaks

How long the high powers last, and the days that set the highest peaks.
- Load duration curve: all quarter-hours of the period sorted from high to low. Read it as: for this many hours, the offtake was at least this high. A curve that falls steeply at the start means the highest peaks only last a few hours, which is where a battery or load shifting pays off.
- Days with the highest peak: the ten days with the highest quarter-hour, with the quarter-hour itself, the peak power and how far it lies above the average monthly peak.
Peak shaving with a battery

What it takes to lower every monthly peak by 10, 20 or 30%.
The table shows what it takes to lower every monthly peak by the same percentage:
| Column | What it is |
|---|---|
| Average monthly peak | The average monthly peak after the reduction. |
| Battery power | The power the battery has to deliver in the month with the highest peak. |
| Battery capacity | The energy the battery has to deliver on the heaviest day: everything above the new limit of that month, added up over the day. |
| Quarter-hours with steering | How many quarter-hours in the period lie above the new limit and need the battery. |
| Capacity tariff saving | The lower monthly peaks multiplied by the capacity tariff, over the period. Without a capacity tariff the column says so. |
This is a sizing indication, not a simulation. The battery capacity assumes the battery cannot recharge between two peaks of the same day, so it errs on the safe side. Charging losses, the state of charge at the start of a peak and the other uses of the battery are not taken into account.