Technical specifications

Technical specifications of the Volt DIO: digital inputs, relay outputs and what they can switch, network and Modbus details, power, environmental limits, certifications and failsafe behaviour.

The data of the Volt DIO that you need to design and wire the cabinet.

At a glance

Item Specification
Channels 6 digital inputs (DI) + 6 relay outputs (DO) per module
Relay switching, max 5 A resistive / 2 A inductive per channel, at 250 VAC or 30 VDC
Contact type Form A (normally open) power relay, potential-free
Communication Modbus TCP (server/slave) over Ethernet, TCP port 502
Ethernet 2 × 10/100 Mbps RJ45 switch ports (daisy chain), 1 MAC address
Power supply 24 VDC nominal (12 to 36 VDC), 188 mA @ 24 VDC (≈ 4.5 W)
Mounting DIN-rail or wall, 27.8 × 124 × 84 mm, < 200 g
Ambient temperature −10 to 60 °C (standard) or −40 to 75 °C (wide-temperature model)
Isolation 3 kVDC / 2 kVrms, field to logic

Relay outputs and maximum switching capacity

Each of the six outputs is a potential-free Form A (normally open) contact with two screw terminals of its own: R0_NO and R0_C up to R5_NO and R5_C (see Terminal block). There is no NC terminal, so the actuation modes that assume normally-closed contacts (NC-ON, NC-OFF) only describe an installation where an interposing relay provides that contact. This is the hard limit of what one output can switch:

Parameter Value
Maximum switching current 5 A resistive, 2 A inductive, per channel
Maximum switching voltage 250 VAC or 30 VDC (also rated at 110 VAC)
Maximum switching power ≈ 1150 W at 230 VAC or 150 W at 30 VDC (5 A resistive)
Contact type Form A (N.O.) power relay, potential-free
Relay on/off time 1500 ms (max.)
Maximum switching rate 0.3 Hz at rated load (pulse mode)
Mechanical endurance 5,000,000 operations
Electrical endurance 100,000 operations @ 5 A resistive load
Field wiring I/O cable max. 14 AWG (≈ 2.5 mm²), screw terminal block

These ratings are per channel, not a budget for the module, and they are switching limits, not continuous-duty design targets. The inductive rating (2 A) is less than half the resistive one, and motors, pumps, fans, transformers, contactor coils, capacitor banks and LED drivers draw an inrush current several times their nominal current, which erodes the contacts quickly. Size on inrush, not on nominal power, and switch anything substantial through an interposing contactor.

What you can wire directly, and what needs a contactor

Load Directly on the relay output?
230 VAC resistive load ≤ 5 A (≈ 1.1 kW), e.g. small heater Yes
230 VAC resistive load > 5 A (> ≈ 1.1 kW) No, switch an interposing contactor
400 VAC (three-phase) load, any size No, contacts are rated 250 VAC max; use a contactor
Inductive AC load ≤ 2 A (small coil, small pump) Possible; add an RC snubber across the contact
Inductive AC load > 2 A (motor, fan, transformer) No, use a contactor, sized for the load's inrush
DC load ≤ 30 VDC and ≤ 5 A resistive (≤ 150 W) Yes, for inductive DC loads keep to 2 A and add a flyback diode
DC load above 30 VDC No, outside the contact rating

In practice: use the relay output as a command contact for switchgear (contactor coil circuit, an EPO/stop input, an enable input) rather than as the power switch of the load itself. A separate contactor also keeps the cabinet's power wiring away from the module.

A wiring example is on Placement and cabling.

Digital inputs (DI)

Parameter Value
Channels 6, sharing one common (6 points per COM)
Sensor type Dry contact, or wet contact (NPN or PNP)
Dry contact On = short to GND, Off = open
Wet contact (DI to COM) On = 10 to 30 VDC, Off = 0 to 3 VDC
Isolation 3 kVDC or 2 kVrms
Field wiring I/O cable max. 14 AWG (≈ 2.5 mm²), screw terminal block

What the EMS does with an input depends on the function you assign to it, see Assigning ports. A wiring example with a wet contact is on Placement and cabling.

Terminal block

The inputs and relays share one removable 20-pin screw terminal block, numbered top to bottom:

Pin Signal Pin Signal
1 COM 0 11 R1_NO
2 DI0 12 R1_C
3 DI1 13 R2_NO
4 DI2 14 R2_C
5 DI3 15 R3_NO
6 DI4 16 R3_C
7 DI5 17 R4_NO
8 GND 18 R4_C
9 R0_NO 19 R5_NO
10 R0_C 20 R5_C

Each relay channel has exactly two terminals, NO and C (common), and no NC terminal. The 24 VDC supply and the ground pin sit on a separate terminal block on the top panel. Screw torque 3 lb-inch.

Network and protocol

Parameter Value
Ethernet ports 2 × 10/100BaseT(X) RJ45, built-in switch (daisy chain), 1 MAC address
Protocol used by the EMS Modbus TCP (the module is the server/slave), TCP port 502
Addressing Fixed (static) IP address required; note IP, port and Modbus slave ID
Factory default IP 192.168.127.254, netmask 255.255.255.0, no gateway
Configuration Browser-based web console on the module's IP address

Keep the Modbus addressing at its factory setting: the EMS uses the default addresses.

Failsafe behaviour and watchdog

Function Behaviour
Power loss All relays de-energize; the normally-open contacts open. This needs no configuration: the contacts cannot stay closed without coil power.
Communication loss, watchdog disabled (factory default) Every output holds the last value the EMS gave it. A controller crash or a broken network therefore changes no relay at all, as long as the module stays powered.
Communication watchdog Optional, disabled by default. When enabled with a timeout, the module enters safe mode after that long without Modbus TCP communication. The EMS polls the module every control cycle, which keeps the watchdog satisfied while the controller is alive.
Safe status per output Each output has its own safe state (Hold Last, ON or OFF), applied when the module enters safe mode. It has no effect at all while the communication watchdog is disabled.
Safe status latch Once a channel has entered safe mode, its safe status stays latched until it is cleared. The EMS polls the module's watchdog alarm flag, reports it as a device error and clears it once the module is reachable again.

Enable the communication watchdog and the per-channel safe status for every output that carries an emergency stop, whatever its actuation mode. Without them, only a loss of the module's own supply drives the relay to a defined state; a controller or network failure simply leaves the relay where it was. Set the channel's safe status to the value that means stop: OFF for a de-energize-to-stop mode (NO-ON, NC-OFF), ON for an energize-to-stop mode (NO-OFF, NC-ON). With an energize-to-stop mode the watchdog is the only thing that can enforce the stop when the link is down. See Safety and requirements.

The module is not a certified functional-safety device: it carries no SIL or performance-level (PL) rating, and its relays are not safety relays. Where a rated safety circuit is required, the relay output should command a safety relay or contactor that provides that rating, and the safety function must be assessed against the applicable standards (for example EN 60204-1 and EN ISO 13850).

Power supply

Parameter Value
Power input 24 VDC nominal, 12 to 36 VDC
Power consumption 188 mA @ 24 VDC (≈ 4.5 W)
Connection Screw terminal block on the top panel, with ground pin
Earthing Connect the ground pin to the cabinet earth

Size the 24 VDC supply for all modules in the cabinet, and keep the emergency-stop chain in mind: if the stop relies on the module being powered, the supply is part of that chain.

Mechanical and environmental

Parameter Value
Dimensions (W × H × D) 27.8 × 124 × 84 mm
Installation DIN-rail or wall mounting
Operating temperature −10 to 60 °C (standard model) or −40 to 75 °C (wide-temperature model)
Ambient relative humidity 5 to 95%, non-condensing

The relays may malfunction in condensing environments below 0 °C. In unheated or outdoor cabinets, provide heating or dehumidification, and choose the wide-temperature model.

Sizing and design notes

  • Switching latency. The EMS re-evaluates outputs every control cycle (≈ 1 s) and the relay itself takes up to 1500 ms, so allow roughly 2.5 s from decision to contact change. The outputs are not suitable for fast or continuous cycling: the maximum switching rate is 0.3 Hz at rated load.
  • Contact life. 100,000 operations at full load is the electrical limit. For a load that is cycled often (a controllable load following PV surplus), the minimum runtime per activation setting protects the relay as much as it protects the load. See Controllable loads.
  • Keep the relay a command contact. Interposing contactors keep load current, inductive loads and 400 V circuits out of the module.

Next steps

Volt DIOAdding the module on the platform and configuring its ports. Placement and cablingPlacement and cabling across cabinets.