Voltmasters Platform
Device settings
The tabs of a device in the Voltmasters EMS: Settings, Communication, Data, Load Manager, Manual Override and Actions, with the connection settings and the device actions.
The gear in the device overview opens a device. Which tabs you see depends on the type and model of the device.
| Tab | What you do there |
|---|---|
| Settings | The name, the description and the parent device. For a PV inverter or a battery inverter also the billed power. For an energy meter also the metering direction, the measurement type, the phase type and the safety margins for import and export, among others. |
| Communication | The protocol, for example Modbus TCP/IP, with the IP address, port and slave ID, plus the two settings below. |
| Data | The live values of the device, with the value and the timestamp per parameter. See The Data tab. |
| Load Manager | Load management on an energy meter. See Load management. |
| Manual Override | Fixing the power of a device yourself for a period. See Manual override. |
| Alarm | Alarm signalling: the relay output of an IO extension that switches while the device has an active fire alarm. For every device type except irradiance meters and IO extensions. See The Alarm tab. |
| Actions | Commands for that device, such as restarting a battery system. Only for models that support it. |
The Settings tab

- The tabs of the device. An energy meter now also has the Load manager and Alarm tabs, which this screenshot does not show yet.
- The type, brand, model and creation date of the device. You do not change these here.
- The safety margins for export and import are locked. Click the pencil to change them.
- Save stores the changes.
An energy meter also has fields for the metering direction, the measurement type, the location, the phase type and the measurement latency. The question mark next to a field explains what it does.
Billed power
A PV inverter and a battery inverter (PCS) show their Billed power in kVA: the power on which PV control and battery control are billed for that device. It is set when the device is added, from the rating of the model or, when the model has no fixed rating, from the rated power you entered. Only administrators can change it.
The Data tab
The Data tab shows whether a device is delivering live values. That is the first check after adding it, see Adding and verifying devices.
Communication settings
Two settings on the Communication tab determine how the controller handles the connection.
Exclusive or shared TCP connection
Some devices accept only one Modbus TCP connection at a time, others accept several. Per device you can therefore choose whether the connection must be exclusive, so the controller keeps the socket for itself, or may be shared with other clients.
- Choose exclusive for devices that freeze or drop the connection to the controller when a second client connects.
- Choose shared when another system (a monitoring portal, a service laptop, a second EMS client) has to reach the same device at the same time.
Fallback on communication loss
For PV inverters and EV chargers you set a fallback limit per device: the power that applies while the EMS cannot reach the device. Otherwise many devices keep the last setpoint sent, so the limit during a communication failure has to be a deliberate choice.
- Set it low (or to zero) when an uncontrolled asset would violate an export limit or a grid-operator constraint.
- Set it high (full power) when losing production or charging power is worse than briefly running unlimited.
As soon as communication is restored, the EMS controls the device again.
The fallback limit is a safety net, not a control setting. Choose it in line with the grid-connection limits of the site and any DSO RTU obligations.
The Alarm tab
On the Alarm tab you pass a fire alarm of the device on to an external system, such as a fire panel. Choose the IO extension and the Relay output that switches on while the device has an active fire alarm. The output switches off again when the alarm clears.
- Underneath, the contact type of the output tells you whether the contacts are normally open or normally closed, and whether they are closed or open while the alarm is active. Change opens the ports of the IO extension to change it.
- Test lets the controller simulate the alarm on the device for 10 seconds, so the output stays on for 10 seconds. Use it to check the wiring. Save your changes first. The connected system, such as a fire panel, may react as if the alarm were real, so warn the people concerned beforehand.
- The IO extension shows which of its outputs are used for alarm signalling.
- Alarm signalling needs controller version 0.0.338 or later.

Device actions
The Actions tab lists the commands the EMS can send to that device. Which ones are available depends on the brand and model. Supported battery systems can be restarted remotely this way, for example when the system no longer responds or after a fault that requires a restart.
A restart interrupts the operation of the device: the battery stops charging or discharging until the system is back online, and control resumes only once the device reports itself as available again. Do not restart during a period in which the installation must stay controllable, for example during an active telecontrol constraint.