Battery health report

Per battery what happened over the last 30 days at most: live values, observations such as SoC jumps, setpoint deviations and alarms, usage, capacity and efficiency, and an AI summary on request.

The Battery health report shows per battery what happened over a period of at most 30 days: how the battery behaved, which problems occurred, how hard it was used and how its capacity and efficiency hold up. It helps to spot a battery that needs attention before it causes a failure.

Opening the report

Open it from the project menu under Analysis, Reports, Battery health report. The menu item appears on projects with batteries, for every user with access to the project.

The Battery health report of a project: the period filter, the AI summary of the period with the Summarise the period with AI button, and the section of one battery with its module address, inverter, the number of observations and the live values under Right now.

Choose the Period at the top right. A period ends today at the latest and goes back at most 30 days.

AI summary

Summarise the period with AI writes a short summary of the observations, the usage and the capacity of every battery in the chosen period. It is only made when you click the button, and is kept for that period. Check the details below before you act on it.

Per battery

Every battery gets its own section, with its inverter, its serial number or module address, and a count of the observations in the period. Each section has these parts:

  • Right now: the live values read from the controller, such as state of charge, battery temperature, bus voltage and current, the DC breaker and the inverter temperatures. Under Modules right now you see the voltage and temperature per module, when the battery reports them. These values are not part of the period.
  • Over the period: a table with the number of observations and their total duration per category.
  • A section per category with the observations themselves.
  • Usage over the period and Capacity and efficiency.

Observations per category

Over the period: a table with the categories SoC jumps (14 observations), Setpoint deviation (13), Temperature (0), Availability and communication (4) and Safety and protection alarms (3) with their total duration, and below it the SoC jumps section with the largest jump of 28.8 % and the observation Abnormal SoC change detected.
CategoryWhat it shows
SoC jumpsSudden changes of the state of charge that the battery power cannot explain, with the largest jump and the maximum that was expected at that moment.
Setpoint deviationPeriods in which the battery did not follow the power the EMS asked for, with the average and largest deviation, for charging and discharging.
TemperatureTemperature alarms of the BMS and the inverter over the period. Temperatures are not logged over time, so this history is built from those alarms.
Availability and communicationTimes the battery or its inverter could not be reached or was out of control, including a controller that was offline.
Safety and protection alarmsProtection alarms of the battery, such as an over- or undervoltage of a cell.

Observations of the same type are grouped, with how often and on how many days they occurred. Every observation links to the incident with Open in incidents. A muted incident type still counts as an observation and is marked Muted, because muting only stops the notifications.

Usage, capacity and efficiency

Usage over the period with the energy charged and discharged, the equivalent full cycles, the configured SoC band, the lowest, highest and average state of charge and the time against and below the minimum and against the maximum, and Capacity and efficiency with the configured round trip efficiency and the capacity.
  • Usage over the period: energy charged and discharged, the equivalent full cycles, the lowest, highest and average state of charge, and how long the battery sat against its minimum, below it, or against its maximum. A deep discharge to 0 % is listed separately.
  • Capacity and efficiency: the configured round trip efficiency and capacity, the measured round trip efficiency when the inverter measures the battery in a way that allows it, the last and next calibration, and the parameter changes over the period.

When several batteries share one inverter, the charged and discharged energy and the cycles of each battery are a share of the inverter total, marked Shared inverter total.