Device integrations
SunSpec
Supported devices: generic SunSpec energy meters and the Fronius Smart Meter IP, read over Modbus TCP.
Our EMS reads energy meters that speak SunSpec over Modbus TCP. The first meter that runs on this integration is the Fronius Smart Meter IP.
SunSpec energy meters are available from EMS controller version 0.0.341.
Supported devices
| Brand | Model | Description |
|---|---|---|
| Fronius | Smart Meter IP | Fronius energy meter on the network |
| Sunspec | Generic | Any energy meter that publishes a SunSpec meter model |
The integration reads the SunSpec meter models 201 to 204 and 211 to 214: wye, delta, split phase and single phase meters, with integer or float values. The EMS finds the model the meter publishes on its own, there is nothing to choose.
Setup
Network
Connect the meter to the same network as the Voltmasters Controller and give it a fixed IP address. Make sure Modbus TCP (SunSpec) is enabled on the meter and that the controller can reach it.
Add the meter in the platform
Add a device of type Energy meter. For a Fronius Smart Meter IP, choose brand Fronius and model Smart Meter IP; the Slave ID is prefilled with
1. For another SunSpec meter, choose brand Sunspec and model Generic, and fill in the slave ID configured on the meter. Fill in the IP address and the port.Verify
Check on the device page that the power and the phase values come in, and that the sign matches the direction of the power flow.
What the meter reports
- Total active power, and reactive power when the meter publishes it
- Voltage, current and active power per phase
- Grid frequency
- Cumulative imported and exported active energy
Positive power is import. A value the meter does not publish, such as the second and third phase of a single phase meter, shows as not measured instead of zero.
Incidents
The event flags of the meter become incidents on the device: power failure, undervoltage, overvoltage, low power factor, missing sensor and overcurrent.