DSO RTU
EME eCON+ panel
Interfacing Fluvius telecontrole through an EME eCON+ panel over Modbus TCP.
The EME eCON+ is a telecontrole panel that relays the grid operator's Fluvius telecontrole signal to the controller over Modbus TCP, as an alternative to a direct Netflex link. The grid operator is still Fluvius; only the way its signal reaches the EMS differs.
flowchart TD
F["Fluvius"] -->|"telecontrol signal"| E["EME eCON+"]
E -->|"Modbus TCP"| C["Controller"]
C -->|"realised production"| E
The eCON+ converts the Fluvius signal for the controller and writes the production back.
To use it, set the telecontrole provider to EME eCON+ under Configuration → Grid & market → DSO RTU settings.
EME eCON+ requires a recent controller version. If the option does not appear in the dropdown, update the controller first.
Connection settings
Unlike the IO-based operators, the eCON+ carries only a Modbus connection, so there are no IO-port or switch-position assignments to configure. You provide:
| Setting | Description |
|---|---|
| IP address | The address of the eCON+ panel on the local network (required). |
| Port | The Modbus TCP port. Leave empty to let the controller use its default. |
| Slave ID | The Modbus unit ID. Leave empty to let the controller use its default. |
| Mode | The Fluvius telecontrol version the panel exposes: TC4 or TC5. This must match how the panel is configured; the controller reads a different set of values per mode. |
TC4 vs TC5
How much the eCON+ conveys depends on the mode:
- TC4: the basic set, a single active-power limit (as a percentage of the asset's maximum production) and a single reactive-power target.
- TC5: the full set, emergency stop for production and for consumption, separate maximum grid injection and consumption limits, a reactive-power band, per-asset production/consumption caps, and the control reasons behind them.
If the mode configured in the platform does not match the mode the eCON+ panel reports, an incident is raised. Set the mode to match the panel.
Once connected, the grid states received through the eCON+ drive the same curtailment of PV, batteries, EV charging and loads as any other telecontrole provider.