Device integrations
Energy meters
The energy meters the Voltmasters EMS reads: grid meter and submeters, where to set the CT and PT ratios, RS485 addresses, and the connection per brand.
An energy meter gives the EMS the measurements it controls on. The most important one is the grid meter on the grid connection: it is the reference for peak shaving, capacity management and the limits of the connection. Submeters follow a sub-circuit, such as a production installation or a group of loads.
flowchart LR
N["Grid"] --> K["Grid meter"]
K --> B["Site distribution board"]
B --> S1["Submeter on a sub-circuit"]
B --> S2["Submeter on a sub-circuit"]
Current and voltage transformers
On a connection with instrument transformers, the meter sees secondary values. On most meters you set the CT and PT ratios on the meter itself, so it already reports primary-side values: this is the case for Acrel, BMR, the Schneider PM5000 and the Siemens PAC. For the Fluvius A1 meter and the Xemex Smart Connect, you enter the ratios in the EMS. Never set them in both places, or the values are converted twice.
RS485 addresses
- Give every device on the RS485 bus a unique address. The device manual explains how.
- Use the low addresses first: 1, 2, and so on.
- Keep the factory settings for baud rate, parity and stop bits, unless there is a reason to change them.
To make an RS485 device reachable over the network, see RS485 to Modbus TCP.
Brands
| Brand | Connection |
|---|---|
| Acrel | Modbus |
| BMR | Over the network, configured with the BMR software |
| Carlo Gavazzi | Modbus over RS485 |
| Eastron | Modbus TCP or RS485 |
| EME | Modbus TCP |
| Fluvius | P1 or A1 port of the digital meter |
| Phoenix Contact | Modbus TCP |
| Schneider Electric | Modbus |
| Siemens | Modbus TCP |
| Smappee | Local MQTT interface of the gateway |
| Socomec | Modbus TCP |
| Xemex | Modbus TCP, as a bridge to the grid operator’s meter |
| Generic (PLC) | Modbus TCP, through a PLC that fills the register block |
All models per brand are in the overview list.