Supported devices: Acrel ADL400

Our EMS reads the Acrel ADL400, a three-phase DIN-rail energy meter, over Modbus.

Supported devices

Model Description
ADL400 Three-phase DIN-rail energy meter

Default slave ID

The ADL400 leaves the factory on slave ID 1 and accepts 1 to 254. The installations we have seen so far are commissioned on 40, so our EMS proposes 40 when you add the meter. Make sure the value matches the address configured on the meter itself.

Set the voltage and current transformer ratios on the meter before you add it. Our EMS reads the primary-side values, so the meter has to apply the PT and CT ratios itself. A meter left on the default ratios reports the wrong power and energy figures.

What the meter reports

  • Voltage and current per phase
  • Active power per phase and total active, reactive and apparent power
  • Power factor per phase and total power factor
  • Grid frequency
  • Voltage imbalance and current imbalance
  • Cumulative imported and exported active energy