Device integrations
PM5000 series
The Schneider Electric PowerLogic PM5000 series in the Voltmasters EMS: PM51xx to PM56xx over Modbus, all on one public register list.
Our EMS reads the Schneider Electric PowerLogic PM5000 series over Modbus. All models share the same public register list, so one integration covers the whole family.
Supported devices
| Model | Description |
|---|---|
| PM5000 series | PM51xx, PM53xx, PM55xx, PM56xx |
Default slave ID
PM5000 meters use slave ID 1 by default. Make sure this matches the slave ID configured in our EMS, or adjust it on the meter if needed.
Set the voltage and current transformer ratios on the meter before you add it. The meter applies its own VT and CT ratios, so a meter on the medium or high voltage side already reports primary-side values and needs no extra scaling in our EMS.
What the meter reports
- Phase and line voltages
- Current per phase and neutral current
- Active power per phase and total active, reactive and apparent power
- Total power factor
- Grid frequency
- Cumulative imported and exported active energy