Device integrations
Phoenix Contact
Supported devices: EEM-MA370 / EEM-MA371, EEM-MA600 and EEM-MA770 / EEM-MA771 series
Supported devices
We support the following Phoenix Contact energy meters:
- EEM-MA370 and EEM-MA371, including the -R variants
- EEM-MA600
- EEM-MA770 and EEM-MA771, including the -EIP variants
All of them are read over Modbus TCP and configured the same way.
This parameter must be set as shown in the image. If it is not configured this way, you can change it by logging into the web interface using the password adm1n.
Configuration
In the interface of the meter, set the Modbus settings as indicated in the screenshot.
- Modbus TCP should be enabled
- Compatibility mode should be disabled
