Fall-Back Flex: connect at full power in a congestion zone

Fall-Back Flex (also written as fallback flex) is Fluvius' temporary connection formula for businesses in zones with grid congestion. Your customer gets the full requested power; only when the local grid is under pressure does Fluvius send a setpoint through the Netflex cabinet that the installation must respect. Voltmasters EMS processes that setpoint automatically and makes the installation fully compliant with the Fall-Back Flex requirements.

What is Fall-Back Flex?

In parts of Flanders the electricity grid is at its limit. Without extra arrangements, a new or upgraded connection of 100 kVA or more could wait years for a grid investment. With Fall-Back Flex your customer can connect right away, at the full requested power, in exchange for the guarantee that the installation temporarily ramps down to a setpoint sent by Fluvius during congestion.

The control runs over telecontrol: Fluvius installs a Netflex cabinet in the customer cabin and sends setpoints over the IEC 60870-5-104 protocol. The formula is explicitly temporary: it lapses once the planned grid investment is carried out, or it is converted into a flexible connection agreement (FAO).

Full power, except during a congestion event

Outside congestion your customer notices nothing. When Fluvius sends a setpoint, the installation ramps down within 3 minutes and stays below the limit until the signal is released.

Congestion event Time Power Full requested power Fluvius setpoint Fluvius sends a setpoint < 3 min Setpoint respected, full control period Back to full power Normal operation: no restriction Control period (24/7 possible)

How the control works technically

Fluvius sends setpoints through the Netflex cabinet in the customer cabin. The Voltmaster Controller connects directly to that cabinet over IEC 60870-5-104 and treats every setpoint as a hard constraint in the optimisation: battery and PV ramp down in a controlled way, and through the I/O module protocol-less loads switch along too.

From Netflex cabinet to every load, in one control chain

During congestion Fluvius sends a setpoint through the Netflex cabinet. The Voltmaster Controller treats it as a hard constraint, ramps battery and PV down directly and switches protocol-less loads through the I/O module, with real-time feedback to Fluvius.

→ Setpoint during congestion IEC 60870-5-104 ← Measurements & feedback Netflex cabinet Fluvius telecontrol Voltmaster Controller Battery & PV Assets with a protocol Heat pump, cooling… Loads without a protocol Direct control I/O module Volt-free contacts

The Fall-Back Flex requirements, and how the EMS meets them

The Fluvius product sheet sets out a number of technical requirements. With Voltmasters EMS the installation meets every one of them, without your customer noticing anything in day-to-day operation.

Response within 3 minutes

An installation must follow a Fluvius setpoint within 3 minutes.

The Voltmaster Controller processes the setpoint immediately as a hard constraint and ramps battery, PV and loads down well within the time limit.

Setpoint respected for the full control period

The setpoint applies until Fluvius releases the signal, not only at the moment of the control action.

The optimisation stays below the limit for the entire period and feeds the measurements back to the Netflex cabinet in real time.

Controllable 24/7

Control actions are possible at any moment, day and night, including weekends.

The controller runs locally on the installation: the telecontrol link with the Netflex cabinet keeps working even during internet outages.

Connection of 100 kVA or more

Fall-Back Flex applies to larger (medium-voltage) connections in congestion zones.

The Voltmaster Controller is built for this installation class and comes prepared for telecontrol as standard.

Loads without a protocol join in too

Respecting a setpoint rarely works with the battery alone. Large loads without a communication protocol, think heat pumps, cooling units, ventilation or process loads, must be able to switch along during a control action.

That is what the Voltmasters I/O module is for: it controls such loads through volt-free contacts. Based on the real-time measurements the controller decides which loads switch when, so the setpoint is met with as little impact as possible on your customer's operation.

Heat pumps Cooling units Ventilation Process loads
The Voltmaster Controller, the industrial edge controller that processes the Fall-Back Flex setpoints

From application to commissioning

As an installer you go through a fixed process with Fluvius together with your customer. Voltmasters takes care of the technical side: the coupling, the validation and the coordination with Fluvius.

  1. 1

    Application with Fluvius

    Your customer applies for the connection; the zone sheet determines whether Fall-Back Flex applies in the zone. The bid form records the flexibility.

  2. 2

    BRP approval

    Your customer's balance responsible party gives its approval, a fixed step in the procedure.

  3. 3

    Netflex cabinet in the cabin

    Fluvius installs the Netflex cabinet in the customer cabin, the telecontrol interface of the connection.

  4. 4

    Coupling & certification

    Voltmasters connects the controller to the Netflex cabinet over IEC 60870-5-104 and guides the validation and certification, often in a single session.

  5. 5

    In service at full power

    The installation runs at the full requested power and is ready for every control action.

And afterwards?

Fall-Back Flex is explicitly temporary. Once Fluvius has carried out the planned grid investment in the zone, the formula lapses and your customer gets a regular connection. In the meantime it can also be converted into a flexible connection agreement (FAO). The telecontrol coupling you install today remains fully usable either way.

Frequently asked questions about Fall-Back Flex

What is Fall-Back Flex?

Fall-Back Flex is a temporary connection formula from Fluvius for businesses in zones with grid congestion. The customer gets the full requested power; only when the local grid is under pressure does Fluvius send a setpoint via telecontrol that the installation must temporarily respect.

When does a connection qualify for Fall-Back Flex?

Fluvius offers Fall-Back Flex for new or upgraded connections of 100 kVA or more in zones where grid congestion is expected. The Fluvius zone sheets show per zone whether the formula applies.

What is the Netflex cabinet?

The Netflex cabinet is the telecontrol cabinet that Fluvius installs in the customer cabin. Through that cabinet Fluvius sends setpoints to the installation over the IEC 60870-5-104 protocol and receives measurements and feedback.

How quickly must the installation respond to a setpoint?

Within 3 minutes, and the setpoint must be respected for the full control period. Control actions are possible 24/7. The Voltmaster Controller automatically processes every setpoint as a constraint in the optimisation.

What about loads without a communication protocol?

The Voltmasters I/O module controls protocol-less loads through volt-free contacts: heat pumps, cooling units, ventilation and process loads switch along whenever a setpoint requires it.

How long does Fall-Back Flex remain in place?

Fall-Back Flex is temporary: the formula lapses once the planned grid investment in the zone is carried out, or it is converted into a flexible connection agreement (FAO).

What role does the BRP (balance responsible party) play?

The BRP's approval is a fixed step in the application. During a control action the customer carries the imbalance responsibility, which is why the BRP must be on board beforehand.

Is Voltmasters EMS compliant with the Fall-Back Flex requirements?

Yes. The Voltmaster Controller connects to the Netflex cabinet over IEC 60870-5-104, responds within the required 3 minutes, respects the setpoint for the full control period and also controls protocol-less loads through the I/O module. Voltmasters additionally guides the validation and certification with Fluvius.

A Fall-Back Flex project on your desk?

Together we review the zone sheet, the installation design and the telecontrol coupling, and we guide the certification with Fluvius from start to finish.

Ready to make your first project pay off?

Tell us about your next installation. We will show you the platform, help you build the business case and guide you from first quote to certification.