# EMU

> Supported devices: EMU Professional II 3/5 TCP/IP energy meter, read over Modbus TCP.

Source: https://voltmasters.io/en/docs/device-integrations/energy-meters/emu/

Our EMS reads the **EMU Professional II** energy meter over **Modbus TCP**. It can serve as grid meter or as submeter.

> **Note**
>
> The EMU Professional II is available from EMS controller version **0.0.341**.

## Supported devices

| Model | Description |
| --- | --- |
| Professional II 3/5 TCP/IP | Three-phase energy meter with a network interface |

## Setup

1. **Network**
   
   Connect the meter to the same network as the Voltmasters Controller and give it a fixed IP address.
2. **Current and voltage transformers**
   
   Set the CT and VT ratios on the meter itself. The meter then reports primary-side values, and there is no ratio to fill in in the EMS.
3. **Add the meter in the platform**
   
   Add a device of type **Energy meter**, with brand **EMU** and model **Professional II 3/5 TCP/IP**. Fill in the IP address and the port. The **Slave ID** is prefilled with `1`, the factory default.
4. **Verify**
   
   Check on the device page that the power and the phase values come in, and that import shows as positive power.

## What the meter reports

-   Active, reactive and apparent power, in total and per phase
-   Voltage and current per phase, and the power factor
-   Grid frequency
-   Cumulative imported and exported energy

## Frozen values

The Professional II sometimes keeps serving the same set of values for up to a minute. The EMS follows the clock of the meter: when that clock has stood still for more than 10 seconds, the EMS stops using the values, so it does not steer on old measurements. After 15 seconds the warning **Device data is stale** appears on the device. When the meter serves fresh values again, the EMS picks them up by itself.

> **Warning**
>
> While the values of the grid meter are stale, the EMS falls back to its safeguards for a missing grid meter, for example the battery stops after a short grace period. When the warning keeps coming back, check the network connection and the firmware of the meter.