# EM24

> Configure the Carlo Gavazzi EM24 for the Voltmasters EMS, including the MEASurE mode that makes the meter report both import and export power.

Source: https://voltmasters.io/en/docs/device-integrations/energy-meters/em24/

### Configuration

Check that the Carlo Gavazzi meter is set to read both import and export power. An unsuitable mode may lead to:

-   Missing readings of feed-in, or
-   Feed-in being counted as offtake (on top of the ‘actual offtake’)

You can set this in the ‘MEASurE’ configuration menu on the energy meter. This should be set to ‘b’.

Warning

**Warning**

This setting may not be present on MID certified models (model numbers ending in PFA and PFB).

![Image 1](https://voltmasters.io/assets/docs/carlo-gavazzi-em24-config-1.webp)

> **Note**
>
> **NOTE: RS485 Device Addresses**
> 
> -   You MUST give each device on the RS485 bus a unique address. Check the manual of the device on how to do this.
> -   Use lower addresses first (1, 2, ...)
> -   For each device, it is generally recommended to stick with the factory default baud rate, parity, and stop bits.
> 
> Set the Modbus address through the power meter's “Address” configuration menu.